PLANNING INFORMATION
MODEL OPTIONS
There are three sizes of Thermador Pro Grand
®
Ranges to choose
from36-inch, 48-inch and 60-inchin your choice of all-gas or
dual-fuel congurations. All models are 27-inches deep and available
in stainless steel with porcelain cooktop. Be sure to reference the
correct model information in this design guide.
INSTALLATION CONSIDERATIONS
The information in this design guide provides key features, product
dimensions, cutouts and installation specications. Before installing a
Thermador Pro Grand Range, be sure to verify the cutout dimensions
and electrical / gas connections. Also, always consult with the
installation manual packed with the product for complete details
before installing.
INSTALLATION OPTIONS
Thermador Pro Grand Ranges feature a bold, professional design and
a commercial-depth of 27-inches. These ranges can be installed in a
wall or island installation.
BACKGUARDS
When using the Flush Island Trim, Thermador recommends a
minimum 12" (305 mm) rear clearance to a combustible surface (see
Figure 1, Cabinet Clearances). Clearances from non-combustible
materials are not part of the ANSI Z21.1 scope and are not certied
by CSA. Clearances of less than 12" (305 mm) must be approved by
the local codes and / or by the local authority having jurisdiction.
NATURAL GAS OR LP
Thermador Dual-Fuel Pro Grand Ranges are shipped by the factory
to operate on natural gas. They must be converted for use with
propane. Verify that the type of gas being used at the installation site
matches the type of gas used by the appliance. If the location / job
site requires conversion from natural gas to propane (LP), utilize the
included LP kit. Field conversion must be done by qualied service
personnel only. Please refer to the LP Conversion Instructions for
further information.
HIGH ALTITUDE
A high altitude kit is available through Customer Services as service
part number 746376.
VENTILATION REQUIREMENTS
We strongly recommend that a Thermador Professional
®
Wall or Island
Hood or Custom Insert be installed with all Thermador Pro Grand
Ranges. Downdraft ventilation should not be used. Do not install a
microwave-hood combination above the cooktop, as these types of
units do not provide the proper ventilation and are not suitable for
use with Thermador Pro Grand Ranges.
Due to the 27-inch commercial-depth of Pro Grand Ranges, the PH
Professional Series Wall Hoods or Professional Series Custom Inserts
would provide the appropriate depth from the wall to correspond to
these ranges.
For high output gas cooktops (60,000 BTU or greater), the minimum
of one (1) CFM of ventilation per 100 BTU is recommended. If the
cooktop has a grill or griddle, add 150 CFM to the estimated blower
capacity. Additional blower capacity may be required for longer
duct runs.
The following table indicates the ventilation hood options that are
recommended for use with Thermador Pro Grand Ranges. Refer
to the Ventilation section or www.Thermador.com for a complete
selection of Professional ventilation options, blowers, and accessories.
WIDTH CONFIGURATION
VENTILATION
OPTIONS
36" 4 Burners
w/Grill OR Griddle
36" or 42" Pro Wall Hood
36" Chimney Wall Hood
42" Island Hood
36" Custom Insert
36" 6 Burners 36" or 42" Pro Wall Hood
36" Chimney Wall Hood
42" Island Hood
36" Custom Insert
48" 4 Burners
w/Grill AND Griddle
48" or 54" Pro Wall Hood
48" Chimney Wall Hood
42" Island Hood
36" Custom Insert
48" 6 Burners
w/Grill OR Griddle
48" or 54" Pro Wall Hood
48" Chimney Wall Hood
42" Island Hood
36" Custom Insert
60" 6 Burners with Grill
AND Griddle OR 24"
Griddle
60" Pro Wall Hood
60" Custom Insert